Next:
Oversized ModulesAre you interested in this product?
Get offerE-Houses
Products:
General specification:
● Structural Design – Eurocode and DNV 2.7-3
● Coating – NORSOK M501 system 1
● A60 personnel doors
● A60 insulation
● Data floor (800mm)
● Monorail WLL: 2500kg
● MCT frames
Ventilation:
● Air Handling Unit
● Cooling and heating
Electrical/HVAC installation:
● NEK 420, NORSOK E-001, NORSOK H-003, EX/ATEX
● Cableladders
● Lights and switches
● PA system
● ExII-Telephone ExResistTel
● Ribheater
● First Aid Case offshore
● Eye wash station 2l
● Fire and gas dampers
Alarm system:
● Fire detectors, smoke detectors
EXTERNAL DIMENSIONS (mm)
Length
17910
Width
4305
Height
5291
WEIGHT (kg)
MGW
52000
Payload
23800
Tare
28200
General specification:
● DNV 2.7-3 R30 approved module
● Structural design acc. EUROCODE
● Zone classification (ATEX / EX) – Zone 2 NORSOK Z-015
● Lifting lugs EN 10204,3.2.
● SS316 Hatch leaf DNV certified (A60)
● Thermal insulation rockwool 60 mm
● 6Mo stainless steel pneumatic tubing
● 50 mm stainless steel skidding plates
● Paint sys.2B (thermally sprayed zinc) -NORSOK M-501
Ventilation:
● Duct heater 3kW
● 5 air changes per hour
Electrical/HVAC installation:
● Electrical installation EX-zone 2
● HFFR – LS cables
● Humidity transmitter
● Temperature transmitter
● Differential pressure transmitters
● Fire dampers
● Goosneck air outlet
● Water leakage detectors
Alarm system:
● Sensors for Flow, pressure and temperature on in- and outlet
EXTERNAL DIMENSIONS (mm)
Length
6140
Width
4134
Height
3760
INTERNAL DIMENSIONS (mm)
Length
5700
Width
3300
Height
3000
WEIGHT (kg)
MGW
25000
Payload
9600
Tare
15400
Uniteam offers Offshore Pressurized Modules designed to hold gases or liquids at different pressures. Units meet various delivery requirements with a range of filling capacities. The Offshore Pressurized modules are built according to DNV 2.7-1 and DNV 2.7-2 standards, with A60 fire-rated panel and ex-proof apparatus for working in hazardous Zone I/II.
Features:
● Flexible dimension and layout
● Customized
● A60 fire rated
● PLC-controlled fire and gas detection
● Suitable for Zone I/II and safe area
Certification:
● DNV 2.7-1/DNV 2.7-2/EN12079
● NORSOK Z-015
● ATEX, IECEx
Application:
● H2S Shelter
● Workshop
● Operating room
● Laboratory cabin
● Living quarters
● Offices
Custom-made Instrumentation Container certified according to DNV 2.7-1, manufactured in accordance with NORSOK Z-015 and special customer demands.
General specification:
● One-off production to optimize solution for the client’s equipment
● 4,0 mm corrugated steel plates in the walls
● A 60 insulation; 70mm in the walls and 100 mm in the ceiling
● 2,0 mm painted, galvanized plates as lining
● Special PVC flooring
● Offshore grids
● Tare: 8000 kg
Features:
● Special lining to meet requirements for heavy equipment
● Reinforced floor and pneumatic sliding doors
Electrical installation
● 690/400 V 60Hz 3 phase
● EX ceiling lights (400 lux)
● EX sockets
● PA cabling
● Wall mounted EX approved heater (1000 W)
● Fire and gas detection/alarm system: Autronica System Interface solutions: specially adapted to the vessel where to be used
● HVAC: EX approved; positive inside overpressure 100 Pa
EXTERNAL DIMENSIONS (mm)
Length
8000
Width
3000
Height
3131
INTERNAL MEASUREMENTS (mm)
Length
7800
Width
2800
Height
2980
Custom-designed Over Pressurized Modular Control Room and Office for offshore use. In compliance with both DNV 2.7-2 and NORSOK Z-015. EX approved for use in Zone 1 and built with overpressure and airlock.
General specification:
● DNV 2.7-1 approved module
● In compliance with DNV 2.7-2/NORSOK Z-015
● EX approved for Zone 1
● SpreFix isolation and 25mm sound isolating sandwich plates as lining
● Airlock to maintain overpressure integrity
● Stainless steel personnel door
Electrical installation:
● Exd and Exe Shutdown panel
● 4 EX approved light fixtures with emergency battery back-up
● EX approved 1000 W Rib heater
● Sockets for 230V
● 3 kW UPS for 20 minutes
● 21 KVA transformer
Ventilation:
● 2 EX actuator driven fire dampers
● 3 kW EX heating element in air duct
Alarm system:
● Optical gas sensor
● Fire alarm system with manual call point
● Smoke detectors
EXTERNAL DIMENSIONS (mm)
Length
6058
Width
2438
Height
2591
Are you interested in this product?
Get offer