search
Inside an Over Pressurized Modular Control Room.

Are you interested in this product?

Get offer

E-Houses

Products:

General specification:
● Structural Design – Eurocode and DNV 2.7-3
● Coating – NORSOK M501 system 1
● A60 personnel doors
● A60 insulation
● Data floor (800mm)
● Monorail WLL: 2500kg
● MCT frames

Ventilation:
● Air Handling Unit
● Cooling and heating

Electrical/HVAC installation:
● NEK 420, NORSOK E-001, NORSOK H-003, EX/ATEX
● Cableladders
● Lights and switches
● PA system
● ExII-Telephone ExResistTel
● Ribheater
● First Aid Case offshore
● Eye wash station 2l
● Fire and gas dampers

Alarm system:
● Fire detectors, smoke detectors

EXTERNAL DIMENSIONS (mm)

Length

17910

Width

4305

Height

5291

WEIGHT (kg)

MGW

52000

Payload

23800

Tare

28200

General specification:
● DNV 2.7-3 R30 approved module
● Structural design acc. EUROCODE
● Zone classification (ATEX / EX) – Zone 2 NORSOK Z-015
● Lifting lugs EN 10204,3.2.
● SS316 Hatch leaf DNV certified (A60)
● Thermal insulation rockwool 60 mm
● 6Mo stainless steel pneumatic tubing
● 50 mm stainless steel skidding plates
● Paint sys.2B (thermally sprayed zinc) -NORSOK M-501

Ventilation:
Duct heater 3kW
● 5 air changes per hour

Electrical/HVAC installation:
● Electrical installation EX-zone 2
● HFFR – LS cables
● Humidity transmitter
● Temperature transmitter
● Differential pressure transmitters
● Fire dampers
● Goosneck air outlet
● Water leakage detectors

Alarm system:
Sensors for Flow, pressure and temperature on in- and outlet

EXTERNAL DIMENSIONS (mm)

Length

6140

Width

4134

Height

3760

INTERNAL DIMENSIONS (mm)

Length

5700

Width

3300

Height

3000

WEIGHT (kg)

MGW

25000

Payload

9600

Tare

15400

Uniteam offers Offshore Pressurized Modules designed to hold gases or liquids at different pressures. Units meet various delivery requirements with a range of filling capacities. The Offshore Pressurized modules are built according to DNV 2.7-1 and DNV 2.7-2 standards, with A60 fire-rated panel and ex-proof apparatus for working in hazardous Zone I/II.

Features:
● Flexible dimension and layout
● Customized
● A60 fire rated
● PLC-controlled fire and gas detection
● Suitable for Zone I/II and safe area

Certification:
● DNV 2.7-1/DNV 2.7-2/EN12079
● NORSOK Z-015
● ATEX, IECEx

Application:
● H2S Shelter
● Workshop
● Operating room
● Laboratory cabin
● Living quarters
● Offices

Custom-made Instrumentation Container certified according to DNV 2.7-1, manufactured in accordance with NORSOK Z-015 and special customer demands.

General specification: 
● One-off production to optimize solution for the client’s equipment
● 4,0 mm corrugated steel plates in the walls
● A 60 insulation; 70mm in the walls and 100 mm in the ceiling
● 2,0 mm painted, galvanized plates as lining
● Special PVC flooring
● Offshore grids
● Tare: 8000 kg

Features: 
● Special lining to meet requirements for heavy equipment
● Reinforced floor and pneumatic sliding doors

Electrical installation
● 690/400 V 60Hz 3 phase
● EX ceiling lights (400 lux)
● EX sockets
● PA cabling
● Wall mounted EX approved heater (1000 W)
● Fire and gas detection/alarm system: Autronica System Interface solutions: specially adapted to the vessel where to be used
● HVAC: EX approved; positive inside overpressure 100 Pa

EXTERNAL DIMENSIONS (mm)

Length

8000

Width

3000

Height

3131

INTERNAL MEASUREMENTS (mm)

Length

7800

Width

2800

Height

2980

Custom-designed Over Pressurized Modular Control Room and Office for offshore use. In compliance with both DNV 2.7-2 and NORSOK Z-015. EX approved for use in Zone 1 and built with overpressure and airlock.

General specification:
● DNV 2.7-1 approved module
● In compliance with DNV 2.7-2/NORSOK Z-015
● EX approved for Zone 1
● SpreFix isolation and 25mm sound isolating sandwich plates as lining
● Airlock to maintain overpressure integrity
● Stainless steel personnel door

Electrical installation: 
● Exd and Exe Shutdown panel
● 4 EX approved light fixtures with emergency battery back-up
● EX approved 1000 W Rib heater
● Sockets for 230V
● 3 kW UPS for 20 minutes
● 21 KVA transformer

Ventilation:
● 2 EX actuator driven fire dampers
● 3 kW EX heating element in air duct

Alarm system:
● Optical gas sensor
● Fire alarm system with manual call point
● Smoke detectors

EXTERNAL DIMENSIONS (mm)

Length

6058

Width

2438

Height

2591

Are you interested in this product?

Get offer
Get Offer